Applications: Data Centers
Pages 233–242 (10 pages)
Text on page 240
Data Center Energy Storage Applications 100 ms-1s Runtime
160 s Runtime
110 min Runtime
0.54 h Runtime
412 h+ Runtime
Power filtering
Synchronous compute loads
Brown-outs, grid supply interruptions
Demand response, renewables integration
Grid resilience
Supercapacitors, NiZn
Supercapacitors, lead-acid, Li-ion LTO, Na-ion NFPP, NiZn
Lead-acid, Li-ion LTO, LFP, Na-ion NFPP, NiZn
Li-ion LFP, Na-ion NFPP
Li-ion LFP, Na-ion NFPP, flow batteries
In-rack in IT room
Rack-level in power room
Rack-level in power room
Grid/utility input side
Grid/utility input side
Data center energy storage requirements differ by runtime, driving demand for distinct performance characteristics that cannot be addressed by a single battery solution.
Source: ZincFive, Peak Energy, Etica AG
Extracted from the PDF; charts and images may read imperfectly.
Page 240 · 8/10